Trap Probes
|
|
|
![]()
Trap Probes are SNMP messages sent by the agent to the manager. When an event occurs, the monitored device send a UDP packet alert to XRatel OPC Server. The most common traps with its OID are:
Trap Probes Configuration
Trap Probes need to be added manually. Add a new Raw Probe. In the Probe Properties dialog, specify the Probe Name, the SNMP OID of the trap, and then, select Trap Probe in Probe Type field. Click on OK button to apply the changes.
XRatel OPC Server supports variables in trap Probes too. To add variables to a trap, open its Probe Properties dialog and in the SNMP OID field insert the trap OID and variables separeted by ";" like in:
<SNMP OID>;<Variable1>;<Variable2>;...;<VariableN>
So, to manage the linkDown trap of the interface 1.3.6.1.2.1.2.2.1.1.3(ifIndex) insert:
1.3.6.1.2.1.11.0.2;1.3.6.1.2.1.2.2.1.1.3 If the above variable is missed, the server will alert a linkDown trap without specifying the source interface.
When a trap is received by the XRatel OPC Server, a hold time is applied to it. This field is defined in Device Settings dialog.Select the desired device in Probe List and then click on Device Properties button. The Trap Hold Time field indicates the hold time in milliseconds. |
|
|